Relay Outputs (Type R)

The modules of the R-series (e.g., XEP01R, XSP01R) feature mechanical relays. These provide galvanic isolation and can also switch AC voltages.

Technical Data

ParameterValue
Contact TypeNormally Open (NO)
Switching Voltagemax. 30 VDC / 250 VAC
Switching Currentmax. 3 A (resistive load)
Electrical Lifemin. 100,000 cycles (at 3A load)
Mechanical Lifeapprox. 10×106 cycles
Relay TypeTyco PCN-124D3MHZ

Relay Power Supply (+Us)

IMPORTANT: 18V Minimum Voltage

The relay coils require at least 18 VDC at terminals Us+ / Us- to pull in reliably. The 12V range (as with the L-series) is not sufficient here!

Output Pin Assignment

The terminal pairs represent potential-free normally open contacts.

BitTerminalDescription
0O0 / O0Relay contact Bit 0 (NO)
1O1 / O1Relay contact Bit 1 (NO)
2O2 / O2Relay contact Bit 2 (NO)
3O3 / O3Relay contact Bit 3 (NO)
4O4 / O4Relay contact Bit 4 (NO)
5O5 / O5Relay contact Bit 5 (NO)
6O6 / O6Relay contact Bit 6 (NO)
7O7 / O7Relay contact Bit 7 (NO)

Safety at 230V

When switching mains voltage (230 V AC), the applicable VDE regulations and protection against contact measures must be strictly observed. Work on mains voltage may only be carried out by qualified personnel.